Many air conditioning systems incorporate a TXV style metering device as the standard. It is extremely important for the HVAC technician to understand the design and
operation of these valves. If proper service practices are not followed, severe system damage will result. When charging a system, follow the manufacturer’s
recommendations. If extra charge is required due to long line sets and the system incorporates a TXV metering device, charging should be done with respect to subcooling at highest load. The greatest chance for a TXV to lose control of the evaporator load is during this time. -If subcooling is present during highest load, enough refrigerant is circulating throughout the system to control the evaporator loads. To adjust evaporator coil superheat, follow the manufacturer’s recommendations. If these are not available, the following guide lines could apply, depending upon the system design temperature:
High Temp   8°F - 12°F
Medium Temp    5°F - 8°F
Low Temp     2°F - 6°F

 

Thermostatic Expansion Valve

P1 = Bulb Pressure (Opening Force)
P2 = Evaporator Pressure (Closing Force)
P3 = Superheat Spring Pressure (Closing Force)
P4 = Liquid Pressure (Opening Force)

 

TXV Pressure Balance Equation
        P1 + P4 = P2 + P3

Disclaimer: The information provided within this publication / eBook/ content is for general informational purposes only. While we try to keep the information up-to-date and correct, there are no representations or warranties, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the information, products, services, or related graphics contained in this publication / eBook/ content for any purpose. Any use of this information is at your own risk.