 Q: What does the ‘MOPD’ rating on solenoid valves mean?
Solenoid valves are rated in terms of Maximum Operating Pressure Differential (MOPD) against which the valve will open. For example, with the valve closed against an inlet pressure of 250 psi and an outlet pressure of 50 psi, the pressure differential across the valve is 250-50 or 200 psi. The MOPD rating for the valve is the maximum pressure differential against which the valve will reliably operate. If the pressure differential is higher than the rated MOPD for the valve, the valve will not operate. The temperature of the coil winding and the applied voltage has a signifi cant affect on the MOPD rating. The MOPD is reduced as the coil temperature increases or the voltage decreases. For this reason the MOPD rating is established by operating the valve at 85% of rated voltage after the coil has attained its maximum temperature by operating at full rated voltage.


Q: Why do some valves have a ‘Min OPD’ rating and what does this mean?
‘Min OPD’ stands for Minimum Operating Pressure Differential. All pilot operated valves (like our 200 and 240 series) require a small amount of pressure differential to
enable the piston or diaphragm to raise off the main seat. Typically, 2 to 5 psig diff erential is needed to accomplish this. If the pressure differential is less than the Min OPD, the valve will not open when actuated or will fail to remain open. If a valve is greatly oversized for the application it can suffer from this effect since the pressure drop across the valve with low flow rates can be below the Min OPD. Direct operating solenoids (like our 50RB and 100RB) do not have a Min OPD specification since they do not rely on system pressures for operation.


Q: What are some typical problems I can expect with a solenoid valve and how do I recognize it?

                     Solenoid Valves Troubleshooting Chart

PROBLEM CAUSE
                  Won't Open Valve Oversized
Not within 10% Rated Voltage
Coil Burnout
Bent Enclosing Tube
Improper Wiring
                  Won't Close Broken Internal Parts
Installed Backwards
Foreign Material In Orifi ce Area
Manual Stem Front-Seated
       Intermittent Operation Transformer Undersized
Valve Oversized For Application
(Pressure Drop Below Min OPD)

 

 

 

Disclaimer: The information provided within this publication / eBook/ content is for general informational purposes only. While we try to keep the information up-to-date and correct, there are no representations or warranties, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the information, products, services, or related graphics contained in this publication / eBook/ content for any purpose. Any use of this information is at your own risk.